OMICRON

QuickCMC

QuickCMC: Test View

QuickCMC: Test View

QuickCMC provides an easy and intuitive user interface, while also offering powerful functions for performing manual tests for all kinds of protection relays, measurement transducers and other equipment.

Features
  • Simultaneous control of all available test signals (voltage and current outputs) of the CMC test set in magnitude, phase, and frequency
  • Steady state, step or ramp function for all quantities
  • Fault Calculator providing different operation modes
  • Timing measurements
  • Vector view and impedance plane
Output functions
Fault Calculator: Output Functions

Fault Calculator: Output Functions

Output quantities can either be entered in the classical way as voltages and currents, or by using input modes for absolute or relative impedance values, powers or symmetrical components.
The module includes the Fault Calculator which automatically converts the entered values to determine the correct output quantities (voltage, current and phase angle) for single-, two- and three-phase faults, power flow, or symmetrical components. The residual voltage and current is also automatically calculated and generated.

The Unit Manager function allows for easy toggling between the handling of values in primary/secondary, absolute/relative, or seconds/cycles.

Step or Ramp Mode
QuickCMC: Vector View

QuickCMC: Vector View

Step or Ramp Mode operation is provided for finding limiting values, such as pick-up and drop-off, or starting of a relay.
In Step Mode, the selected quantities (currents, voltages, impedances, power, etc.) are increased or decreased by a specified value with a mouse click.
In Ramp Mode, the defined step is repeated until an input toggles (e.g. when the relay trips). The pulse ramping functionality allows easy testing of protection elements with overlapping characteristics (e.g. testing the I >> threshold).

Input/measuring functions

10 binary inputs can be used to monitor dry or wet contacts and make corresponding time measurements. The time measurement may alternatively trigger on the external interruption of the generated currents, allowing direct assessment of CB contacts. The output values of a transducer connected to the analog DC inputs can also be displayed.

Reporting

Results of tests with QuickCMC can be stored for later use. Similar to all other testing modules in the OMICRON Test Universe software, the report style and content can be customized. In addition, the QuickCMC reporting feature provides a “notepad” function, so that individual comments may be added to the report.