В этом разделе представлены письменные материалы, созданные группой инженеров компании и пользователями испытательных комплектов OMICRON для публикации на различных конференциях и в различных журналах. Зарегистрированные клиенты могут получить доступ к дополнительным документам и указаниям по применению в Клиентском разделе!

TitleYear of PublicationConference / Magazine

New Approach to assess the insulation condition of instrument transformers (411 KB)

S. Raetzke, M. Koch and M. Krueger, OMICRON, Austria

Dielectric response analysis is an advanced technique, providing information about the insulation condition of the measured test object. This paper introduces a new approach to use the dielectric response analysis for condition assessment of instrument transformers.

2011ISH, Germany

Technology of the future - Sampled Values provide many benefits for the power systems of tomorrow (205 KB)

Fred Steinhauser, OMICRON, Austria

IEC 61850 defines several kinds of communication mechanisms. The Client/Server communication for SCADA and the GOOSE protocol for peer-to-peer status messaging have been widely adopted in a quite short time. Now, after years of experience with these new protocols, also the application of Sampled Values has become a common topic.

2011OMICRON Magazine

Synchronous 3-Phase Partial Discharge Detection on Rotating Machines (593 KB)

W. Kalkner, A. Obralic, Technical University Berlin
R. Plath, IPH High Voltage Lab
M. Kaufhold, A. Bethge, Siemens, A&D Large Drives

The paper describes the technical characteristics of a new synchronous digital PD measurement system as well as the theory and abilities of a new evaluation technique, which enables the separation of multiple PD sources from each other and from outer noise.

2006Cigre, France

New Aspects of Manual Protection Testing (517 KB)

Thomas Schossig & Stefan Schwabe, OMICRON, Austria

The challenges of commissioning and routine testing are diverse. This paper describes which new possibilities arise through innovative approaches in the control unit of the applied test sets.

2010Transmission & Distribution, Australia
Explore new paths with the CT Analyzer – Extended testing benefits for your applications (764 KB)

Florian Predl, OMICRON, Austria

This paper describes on the one hand side the principal test procedure of the CT Analyzer and points out the advantages of this test method in regards to a conventional high current injection measurement method. On the other hand side it elucidates special current transformer testing applications and reveals attempts at solutions. Furthermore, the CT Analyzer PC Tools are introduced and their advantages and possibilities for the individual user are presented.
2010ITMF, Austria

Setting up a SCADA Controlled Distribution Automatic Restoration Systems' Tests (472 KB)

John Witte, Orange & Rockland, USA
David Marble, OMICRON, USA

The new generation of reclosers and sectionalizers with their new abilities and digital controllers put much higher demands on the test personnel and the test equipment used. This paper discusses the new challenges in detail and shows how they can be mastered.

2011IPTS, Austria
 

Information within the Dielectric Response of Power Transformers for Wide Frequency Ranges (571 KB)

Michael Jaya, Thomas Leibfried, Institute of Electric Energy Systems and High-Voltage Technology (IEH), University of Karlsruhe (TH)
Maik Koch, OMICRON

Dielectric response analysis of power transformers in the frequency domain is being used widely to diagnose its aging condition and moisture content. Winding resonance effects were noticed at higher frequencies and it appears that the response at higher frequencies is not purely of dielectric nature. Higher frequencies are therefore unsuitable to determine the insulation aging of power transformers. For low frequencies, the dielectric response reflects the properties of the oil, the interfacial polarization effect and the cellulose material. Conducting the measurement over a wide frequency range enables for discriminating between these different properties and increases the accuracy of moisture calculation.

2010IEEE ISEI, 
San Diego, USA

New Approach to Simulation Based Type Testing of Protection Relays (331 KB)

Stefan Schwabe, OMICRON

This paper discusses the advantages of using transient simulation for assessing protective relays. It shows why even upcoming standards for type testing are relying on this method. Furthermore, the importance of statistical methods for investigating the behavior of algorithms is described. 

2011IPTS, Austria

Reliable Moisture Determination in Power Transformers (454 KB)

Dr. Maik Koch, OMICRON

This article describes and compares methods for reliable assessment of moisture in oil-paper-insulated power transformers. The work concentrates on the use of equilibrium diagrams and dielectric response methods for on-site moisture determination. Case studies illustrate the practical application of the achievements.

2010Electra, Germany

Different representations of the ground impedance matching in distance protection relays (251 KB)

Steffen Kaiser, OMICRON

Digital distance protection relays use different algorithms for calculating the line impedance to the fault location from the current and voltage measurements. This paper describes the underlying algorithms and their impact on testing the digital distance protection relays.

-German User Meeting

Dielectric Response Analysis and PD Testing for Condition Assessment of HV Bushings (1.2 MB)

Dr. Michael Krueger, Dr. Maik Koch, OMICRON
Gunther Kopp, ABB / Switzerland; Michael Muhr, TU Graz / Austria

Dielectric breakdown of the HV bushings is one of the most frequent failure causes for power transformers. This paper discusses new diagnostic methods to assess the dielectric condition, including the analysis of the dielectric response and partial discharge measurements, and reports several case studies.

2010CMD, Tokyo

Universal Calibrator for Electrical Quantities for Power Utilities, Industry and R&D (619 KB)

Reinhard Kuntner, OMICRON

The requirements for accuracy, long-term stability, versatility, portability and flexibility of a calibration device providing active current and voltage signals are demanding. This paper shows how the use of cutting-edge technology in hardware and software makes a universal calibrator fulfilling all of these requirements possible.

2009ENME, Mexico

Advanced Insulation Diagnostic by Dielectric Spectroscopy (200 KB)

Dr. Maik Koch, Dr. Michael Krüger, Dipl.-Ing. Markus Pütter OMICRON

This paper discusses and compares dielectric spectroscopy in time and frequency domain to traditional dielectric measurements such as dielectric dissipation factor at power frequency and polarization index. Special focus is given on a comparison of the currently available dielectric spectroscopy methods to traditional measurement techniques like dielectric dissipation factor tests at power frequency and 0.1 Hz, dielectric adsorption ratio and the polarization index.

2009TechCon, Sydney

Cost-optimized Protection & Control System Testing and Commissioning Process in Turnkey HV Substation Project Business (580 KB)

Thierry Canaguier, Quentin Derossi, SIEMENS T&D, France / Dr. Till Welfonder, OMICRON, France

With progressing substation digitalization and increased pressure on turnkey project prices and delivery times, an adaptation of testing and commissioning practices became necessary. An efficient optimization of the substation testing process is possible by anticipated factory testing of interconnected sub-systems, early involvement of dedicated commissioning coordination managers and the use of modern automated equipment.

2010OMICRON International Protection Testing Symposium

Aspects of the Practical Application of Sweep Frequency Response Analysis (SFRA) on Power Transformers (569 KB)

Alexander Kraetge, OMICRON / H. Viljoen, Alectrix South Africa

Sweep Frequency Response Analysis (SFRA) has turned out to be a powerful and sensitive method to evaluate the mechanical integrity of core, windings and clamping structures within power transformers by measuring their electrical transfer functions over a wide frequency range. A summary of guidelines derived from a large number of successful measurements is given to put the reader in a position to achieve a good degree of repeatability, too. 

2009CIGRE / 6'th Southern Africa Regional Conference

Efficient, Easy and Standardized Testing of Electromechanical Relays by Using a Library of Test Templates (372 KB)

Peter Fong, Sequence Instruments, Canada / Michael Albert, OMICRON, Germany

Most of the protection engineers have to test all generations of protection relays - electromechanical, electrostatic and of course digital relays. For these people it will be a tremendous help to have only one test equipment to use. OMICRON provides within its Protection Testing Library a lot of test plans using the same hardware and the newest software for all kinds of protection relays.

2010OMICRON International Protection Testing Symposium
Evaluation of Distance Protection Performance According to the Proposed Standard IEC 60255-121 (614 KB)

Boris Bastigkeit,  OMICRON

The performance of distance protection devices plays a key role in the protection systems of the transmission (and some) distribution networks around the globe. The current efforts of the working group IEC TC 95 MT4 target on standardizing the type testing and verification of this performance.
2010OMICRON International Protection Testing Symposium

Performance Measurements for IEC 61850 IEDs and Systems (569 KB)

Fred Steinhauser, OMICRON

To assess the applicability of an IED, ratings for its communication performance are required. The described methods to assess the performance can be performed with modern, accurate protection test sets and do not require specialized communication test equipment. 

2010PAC World Conference

New diagnostic tools for high voltage bushing (1.1 MB)

Dr. Michael Krüger, OMICRON

Dielectric response measurements in the frequency domain (FDS) or in the time domain (PDC) are applied to transformer insulation to determine the water content in the cellulose. These methods can be applied also for high voltage bushings with good success. 

2010Cigré VI Workspot: International Workshop on Power Transformers

Measurement of line impedance and mutual coupling of parallel lines to improve the protection system (235 KB)

Lutz Hulka, OMICRON

Reliability of transmission widely depends on the reliability of the applied protection system. It is obvious that the main requirements for the protection system are that it is safe, selective and fast. In the case of distance relays, these requirements can only be fulfilled when the mechanisms called "Earth Impedance Compensation" and "Mutual Coupling Compensation" work sufficiently.

2009CIRED
 20th International Conference on Electricity Distribution

The negative dissipation factor and the interpretation of the dielectric response of power transformers (198 KB)

Dr. Maik Koch, OMICRON

This paper presents the appropriate measurement circuit and interpretation scheme of the dielectric response of oil-paper insulated power transformers.

2009ISH 2009

Synchronous Multi-Channel PD Measurements and the Benefits for PD Analyses (645 KB)

Alexander Kraetge, OMICRON

Partial discharge (PD) measurements on transformers, cable systems and rotating machines are a worldwide accepted tool of quality control in factories and under on-site conditions. Common methods to improve the quality of noisy PD data are filtering and gating. Recently a new multi-channel synchronous method has been introduced, capable of separating PD from noise by comparing the amplitude relationship of simultaneous PD of any three channels (3PARD).
2009IEEE T&D

Testing Teleprotection Schemes by Transient Network Simulation (826 KB)

Boris Bastigkeit, OMICRON

The example of "testing distance-teleprotection systems" is used in this article to demonstrate how the simulation of faults on the protected line by means of a network model can substantially simplify testing. Hence, not only the correct parameter setting and function of the protection device are ensured but also the plausibility of the calculated parameter settings is verified.

2009OMICRON International Protection Testing Symposium

Testing Power Quality Meters using a CMC Test Set (558 KB)

Reinhard Kuntner, OMICRON

2007OMICRON International Protection Testing Symposium

Improved Possibilities for Testing of Line Differential Protection (297 KB)

Dr. Peter Meinhardt, OMICRON

2006OMICRON International Protection Testing Symposium

Improved Automated Testing for Protective Relays (501 KB)

Boris Bastigkeit, OMICRON

2006

High Voltage Substation Earth Grid Impedance Testing (195 KB)

Dean Sharafi, Western Power / Ulrich Klapper, OMICRON

2006

Reliability of Transmission by Means of Line Impedance and k-Factor Measurement (302 KB)

Ulrich Klapper, Dr. Michael Krüger, Steffen Kaiser, OMICRON

2006
Longitudinal Induction Voltages on Measurement Communication Cables Running Parallel to Overhead Lines (355 KB)

Dean Sharafi, Western Power
2006
Time saving and simplification of protection testing through the use of the Test Universe Software 2.0 and CM ASB2 switching box at Valorec / Switzerland (237 KB)

Boris Bastigkeit, OMICRON
2005OMICRON User Meeting
Network Simulation on the PC – New Options for Protection Testing (241 KB)

Dr. Fred Steinhauser, OMICRON
2004OMICRON International Protection Testing Symposium
Useful Tools for Substation Commissioning (505 KB)

Reinhard Kuntner, OMICRON
2004OMICRON International Protection Testing Symposium
Testing the pick-up value of overlapping protection elements/functions without changing the parameter settings. (236 KB)

Boris Bastigkeit, OMICRON
2002OMICRON User Meeting
Synchronization of power station generator and power system – Testing the accuracy of a synchronizing device using special EnerLyzer features (1.7 MB)

Boris Bastigkeit, OMICRON
2001OMICRON User Meeting
Efficient Type Testing of Digital Protection Relays (178 KB)

Steffen Kaiser, Reinhard Kuntner, OMICRON
2001
Remote Controlled Testing of Communication Schemes for Power System Protection Using Satelite (GPS) Synchronization and Modern Communication Technology: A New Approach (269 KB)

Zeljko Schreiner, Reinhard Kuntner, OMICRON  
2001
Communication Technology in Substations - Actual Developments from the View of Testing (61 KB)

Dr. Fred Steinhauser, Manish Gupta, OMICRON
2001